Burnham RTC (Return Temperature Control) Folleto Pagina 2

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 4
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 1
2
The concept of boiler protection
has existed for many years.
However, the primary focus in
hydronic systems is often the
demand and delivery design
characteristics. Frequently, little
attention is given to the heat
source – the boiler.
Controlling Return
Temperatures
The Burnham Commercial RTC Return
Temperature Control provides an
economical and effective means of
boiler protection from thermal shock
and sustained condensing operation.
By expanding the “boiler envelope”
to incorporate a 3-way valve and
flow control system, the RTC Return
Temperature Control maintains a
minimum return water temperature of
135°F or greater.
Why Boiler Protection?
Today’s demands for comfort
and efficiency require greater
attention to the temperature and
volume of return water to the
boiler. Many premature boiler
failures can be traced to these two
uncontrolled variables. Operating
below minimum temperatures
and flow rates creates thermal
shock conditions and flue gas
condensation issues, each of which
can shorten the life expectancy of
a boiler. Other factors that affect
return temperature and flow
include:
snow melt and radiant flooring
applications
complex system integration and
control
outdoor reset and warm weather
shutdown
misunderstanding the protection
value of primary/secondary
systems
conversion of steam or gravity
flow systems to pumped water
systems, while retaining the
original oversized distribution
systems
RTC RETURN TEMPERATURE CONTROL
Basic RTC Kit
3 x 12 Nipple with Tapping
24 Vac Actuator
3-way Valve
J-Box
Mounting Bracket
Standard Equipment
RTC Kit with Outdoor Reset
Basic RTC Kit with additional
items below:
917-14 Universal Sensor for Mixing
070 Outdoor Sensor
Additional Components
Boiler Circulator
one required per RTC kit
(not included)
Flange Kits for 3-way valves
available in 2-1/2” to 5” sizes
The RTC system is supplied as a kit
and can be incorporated into most
hydronic hot water applica-tions with
minimal modifications to the system
design and operation. It provides a
simple means for boiler protection and
an opportunity to increase operational
efficiency.
Outdoor Reset Option
The addition of the outdoor reset
option provides additional energy
savings by modulating the system
supply water temperature based upon
outdoor air temperature. This allows
the system to closely match the heat-
ing needs of the building regardless of
weather conditions.
Features Include:
Indoor/Outdoor Reset Control
Thermal Shock and Flue Gas
Condensation Protection
Maintains Minimum Return Water
Temperature
Simple Self-Diagnostic Test
Sequence with Error Messages
Adjustable Boiler Pump Purge
Off-Season Built-in Pump and
Valve Exerciser
24 Vac Floating Motor Actuator on
3-way Valve
Vista de pagina 1
1 2 3 4

Comentarios a estos manuales

Sin comentarios